DEEP BASEMENT METHODOLOGY:
Raft-Dr. Fixit Torchshield:
SURFACE PREPARATION:
1.Clean the surface thoroughly to get rid of all contaminants remove all surface imperfections and repair with a polymer
modified mortar using Dr. Fixit pidicrete URP.
2.Ensure the surface is completely dry before starting installation of Dr. Fixit Torchshield
APPLICATION:
1.Prime the surface using Dr.Fixit Torchshield primer
2.Torch-apply a Dr.Fixit Torchshield AP 4160 membrane by providing an overlap of least 100mm.
3.Lay a second layer of the Dr. Fixit Torchshield AP 3160 membrane with an overlap of 50% above the first layer
4.Place a geotextile fabric of 150 gsm over the membrane before laying the concrete screed of 50mm which will facilitate
the reinforcement cage to be assembled,so the RCC raft can be cast over it.
Retaining wall-Dr. Fixit Torchshield
SURFACE PREPARATION:
Clean the surface thoroghly to get rid of all contaminants.Remove all surface imperfections and repair with a polymer
modified mortar using Dr. Fixit Pidicrete URP.
APPLICATION:
1.Lay Dr. Fixit Torchshield AP 4160,an APP based polyester reinforced membrene,by providing an overlap of at lesat
100mm.
2.Lay a second layer of the Dr. Fixit Torchshield AP 3160 membrane with an overlap of 50% above the first layer.
3.Fix the dimpled or plain protection board as a protective layer over the Torchshield membrane.
4.Backfilling can be done after installation.